美国UE-J120-454-隔爆型压力控制器EXD-美国UE江西代理

发布时间:2022-02-22

J120-451-M200-0500 J120-452 J120-450 J120-453  J120-454

美国UE防爆压力控制器 UE授权代理 原产地:美国

 J120-450美国UE0.5级精度压力开关-UE隔爆压力控制器-危险区域应用

As safety requirements become more stringent, the determining factor in specifying an industrial pressure,differential pressure and/or temperature switch rests upon that switch protecting equipment,processes and personnel. Meeting hazardous location requirements through worldwide approvals and certifications, UE’s 120 Series is the choice where potentially explosive or highly corrosive atmospheres exist.

The 120 Series offers a variety of pressure, vacuum, differential pressure and temperature ranges, as well as process connections, wetted materials and sensor types. With a common flexible platform, models can quickly be adapted at the factory for special requirements, such as ranges, process connections and electrical ratings. Typical industries using 120 Series switches include chemical, petrochemical, refinery and oil & gas production and transmission.

 J120-450美国UE0.5级精度压力开关-UE隔爆压力控制器-危险区域应用

specifications

Storage temperature -65 to 160°F (-54 to 71°C)

Ambient temperature limits -58 to 160°F (-50 to 71°C); models 36-39, 520-525, 540-548, 701-705, 15834-15839:

0 to 160°F (-17 to 71°C); types 820E, 822E: -40 to 160°F (-40 to 71°C) set point

typically shifts less than 1% of range for a 50°F (28°C) ambient temperature change;

less than 2% for types E121& E122

Set point repeatability Temperature models: Type B, C and F: ±1% of full scale range

Type E: ±2% of full scale range

Pressure models 126-164, S126B-S164B, 171-174, 270-274, 358-376, 520-535, 540-

543, 701-705, 15622, 15834,-15839: ±1% of full scale range; models 450-

457, 550-559: ±1/2% of full scale range; models 36-39, 183-194, 483-494, 544-548,

565-567, 612-680, 15875: ±1-1/2% of full scale range Shock Set point repeats after 15 G, 10 millisecond duration Vibration Set point repeats after 2.5 G, 5-500 Hz Enclosure Die cast aluminum, epoxy powder coated; gasketed; cover lock; internal set point lock standard on types J, C, F; gasketed stainless steel tamper-resistant dial cover on types B, H, E; aluminum nameplate Enclosure classification Certified to enclosure type 4X. Class I, Division 1 product meets enclosure type 7; Class II, Division 1 product meets enclosure type 9. Certified to IP66 requirements Switch output One or two SPDT; dual switch may be separated up to * of range; except type 822E where switch #2 can be set up to 25% of range span below switch #1 setpoint; switches may be wired “normally open” or “normally closed”.

Electrical rating* 15A 125/250/480 VAC resistive (standard), 2A @ 30 VDC, 1A @ 48 VDC, 0.5A @ 125 VDC; except types J120-15622, 15834-15839, H121-15875: 20A 125/250/480 VAC resistive, 6A @ 30 VDC, 0.5A @ 125 VDC, 0.25A @ 250 VDC; except types B121-13272, B122-13322, E121-13273, E122-13321: 22A 480 VAC resistive, 2A @ 30 VDC, 1A @ 48 VDC, 0.4A @ 125 VDC.

Reference scales Types B, E & H: external dial

 J120-450美国UE0.5级精度压力开关-UE隔爆压力控制器-危险区域应用