后经变检对6KVⅠ段PT4603进行试验,发现6KVⅡ段PT二次线圈短路;6KVⅠ段4603一次保险熔断是由于该PT二次线圈短路造成的。6KVⅡPT4604一次保险熔断是由于合上6KVPT切换开关后将故障电流转移到II段PT造成事故范围扩大。2)造成PT二次线圈烧毁的原因,除了雷击原因以外,还有PT的一次保险容量选择过大(运行中保险型号RN2-10-1A,应该是0.5A)事后将PT一次保险更换为0.5A。Mitsubishi Breaker NF-SK3300 NF 300 Amp 300A A Ext Lugs