动作方向
|
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
|
|
*持续电压Uc
|
14 V DC
|
|
9.8 V AC
|
|
额定电流
|
450 mA (45 °C)
|
|
UC时,有效工作电流IC
|
≤ 5 µA
|
|
残流IPE
|
≤ 5 µA (适用PT 2X2-BE)
|
|
≤ 1 µA (适用PT 2X2+F-BE)
|
|
标称放电电流In (8/20) µs(线芯-线芯)
|
10 kA
|
|
额定放电电流In(8/20)µs(线芯-地)
|
20 kA ()
|
|
脉冲放电电流Iimp (10/350) µs
|
2.5 kA
|
|
放电电流Itotal (8/20) µs
|
20 kA
|
|
*放电电流Imax (8/20) µs(线芯-线芯)
|
10 kA
|
|
*放电电流Imax (8/20) µs(线芯-地)
|
20 kA ()
|
|
额定功率脉冲电流lan(10/1000)µs(线芯-线芯)
|
67 A
|
|
输出电压限值1 kV/µs(线芯-线芯)波峰
|
≤ 55 V
|
|
输出电压限值1 kV/µs(线芯-地)波峰
|
≤ 55 V (适用PT 2X2-BE)
|
|
≤ 700 V (适用PT 2X2+F-BE)
|
|
输出电压限值1 kV/µs(线芯-线芯)静态
|
≤ 25 V
|
|
输出电压限值1 kV/µs(线芯-地)静态
|
≤ 25 V (适用PT 2X2-BE)
|
|
≤ 40 V (适用PT 2X2+F-BE)
|
|
残留电压 ln,(导线-导线)
|
≤ 25 V
|
|
残留电压 ln,(导线-地)
|
≤ 40 V (适用PT 2X2-BE)
|
|
In下的残压(线-信号地)
|
≤ 25 V (适用PT 2X2-BE)
|
|
残压lan(10/1000)µs(导线-导线)
|
≤ 25 V
|
|
Ian(10/1000)µs下的残压(线-信号地)
|
≤ 25 V
|
|
电压保护水平Up(线芯-线芯)
|
≤ 80 V (C1 - 1 kV / 500 A)
|
|
≤ 100 V (C2 - 10 kV / 5 kA)
|
|
≤ 50 V (C3 - 25 A)
|
|
≤ 80 V (6 kV / 3 kA)
|
|
电压保护水平Up(线-地)
|
≤ 85 V (C1 - 1 kV / 500 A,带PT 2X2-BE)
|
|
≤ 140 V (C2 - 10 kV / 5 kA 带PT 2X2-BE)
|
|
≤ 100 V (6 kV / 3 kA 带PT 2X2-BE)
|
|
≤ 50 V (C3 - 25 A 带PT 2X2-BE)
|
|
电压保护水平Up(线-信号地)
|
≤ 50 V (C3 - 25 A 带PT 2X2-BE)
|
|
≤ 140 V (C2 - 10 kV / 5 kA 带PT 2X2-BE)
|
|
电压防护等级Up静态(线芯-线芯)
|
≤ 25 V (C2 - 10 kV / 5 kA)
|
|
≤ 27 V (C3 - 25 A)
|
|
电压防护等级Up静态(线芯-接地)
|
≤ 45 V (C2 - 10 kV / 5 kA 带PT 2X2-BE)
|
|
≤ 27 V (C3 - 25 A 带PT 2X2-BE)
|
|
电压保护水平Up静态(线-信号地)
|
≤ 25 V (C2 - 10 kV / 5 kA 带PT 2X2-BE)
|
|
≤ 27 V (C3 - 25 A)
|
|
响应时间tA
|
≤ 500 ns
|
|
输入衰减aE,对称。
|
典型值 0.3 dB (≤ 5 MHz / 100 Ω)
|
|
截止频率fg(3 dB),100 Ω对称系统
|
典型值 60 MHz
|
|
电容(线芯-线芯)
|
典型值 30 pF
|
|
每条路径的电阻
|
2.2 Ω ±10 %
|
|
电涌保护故障报警
|
无
|
|
需要的*备用保险丝
|
500 mA (T)
|
|
电涌电流电阻(导线-导线)
|
C2 - 10 kV / 5 kA
|
|
C3 - 67 A
|
|
电涌电流电阻(导线-接地)
|
C2 - 10 kV / 5 kA
|
|
C3 - 67 A
|
|
D1 - 2.5 kA
|