QUINT4-UPS/24DC/24DC/10魏德米勒订货数据:
| 输入电压 | 24 V DC |
| 输入电压范围 | 18 V DC ... 30 V DC |
| *介电强度 | 35 V DC (已进行防反极性保护) |
| 保险丝内部输入 | 无 |
| *电网典型电压 | 24 V DC |
| 电源电压的电压类型 | DC |
| 冲击电流 | ≤ 7 A (≤ 4 ms) |
| 防止极性逆转 | 是 |
| 固定备份阈值 | 22 V DC |
| 30 V DC | |
| 动态触发阈值 | > 1 V / 100 ms |
| 吸合时间 | * 3 s |
| 电池运行中的接通时间(电池启动) | 8 s |
| 电压压降,输入/输出 | 0.4 V DC |
| 电流消耗IN(UN,IOUT = IN,Icharge = 0) | 10.1 A |
| 电流消耗Imax(UN,IOUT = IStat.Boost,Icharge = max) | 16.2 A |
| 电流消耗INo-Load(UN,IOUT = 0,Icharge = 0) | 48 mA |
| 电流消耗Icharge(UN,IOUT = 0,Icharge = max) | 3.5 A |
| 功耗PN(UN,IOUT = IN,Icharge = 0) | 241 W |
| 功耗Pmax(UN,IOUT = IStat.Boost,Icharge = max) | 384 W |
| 功耗PNo-Load(UN,IOUT = 0,Icharge = 0) | 1.2 W |
| 功耗Pcharge(UN,IOUT = 0,Icharge = max) | 90 W |

| 效率 | 典型值 98 % |
| 输出数目 | 1 |
| 防短路保护 | 是 |
| 防空转 | 是 |
| 切换时间 | 0 ms |
| USB并联连接 | 否 |
| UPS串联连接 | 否 |
| 并联电源存储设备 | 是,5(注意线路保护) |
| 串联电源存储设备 | 否 |
| 市电供电 | |
| 输出电压 | 24 V DC (UOUT = UIN - 0.4 V DC) |
| 输出电压范围 | 18 V DC ... 30 V DC (UOUT = UIN - 0.4 V DC) |
| 18 V DC ... 32 V DC | |
| 输出电流IN | 10 A |
| Static Boost (IStat.Boost) | 12.5 A |
| Dynamic Boost (IDyn.Boost) | 20 A (5 s) |
| 选择性熔断 (ISFB) | 60 A (15 ms) |
| 输出功率POUT(UN,IOUT = IN) | 240 W |
| 输出功率POUT(UN,IOUT = Istat.Boost) | 300 W |
| 输出功率POUT(UN,IOUT = Idyn.Boost) | 480 W (5 s) |
| 功耗 无负载(UN,IOut = 0,ICharge = 0) | 3 W |
| 功耗 标称负载(UN,IOut = IN,ICharge = 0) | 8 W |