出售 全新原装进口 BECKHOFF倍福 EL3318
The EL3318 analog input terminal allows eight thermocouples to be connected directly and is thus particularly suitable for space-saving use in control cabinets. The EtherCAT Terminal circuit can operate thermocouple sensors using the 2-wire technique. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminal. The EL3318 can also be used for mV measurement.
The HD EtherCAT Terminals (High Density) with increased packing density feature 16 connection points in the housing of a 12 mm terminal block.
| Technical data | EL3318 |
|---|---|
| Number of inputs | 8 |
| Power supply | via the E-bus |
| Thermocouple sensor types | types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement |
| Connection method | 2-wire |
| Wiring fail indication | yes |
| Conversion time | approx. 5 s up to 40 ms, depending on configuration and filter setting, see documentation, default: approx. 500 ms |
| Measuring range |
in the range defined in each case for the sensor (default setting: type K; ‑100…+1,370 °C); mV measurement: ±30 mV…±75 mV |
| Resolution | 0.1 °C per digit |
| Measuring error | < ±0.3 % for type K (relative to full scale value), further types see documentation |
| Electrical isolation | 500 V">rms (E-bus/signal voltage) |
| Current consumption E-bus | typ. 210 mA |
| Bit width in the process image | 8 x 32 bit TC input, 8 x 16 bit TC output |
| Configuration | no address setting, configuration via the controller |
| Conductor types | solid wire, stranded wire and ferrule |
| Conductor connection | solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver |
| Rated cross-section | solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm² |
| Weight | approx. 70 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. /installation pos. | IP 20/variable |