CU230P‑2 PN Control Unit
The Control Unit performs closed-loop control functions for the inverter.
The CU230P-2 Control Units are designed for drives with integrated technological functions for pump, fan and compressor applications.
The I/O interface, the fieldbus interfaces and the additional software functions optimally support these applications. The integration of technological functions is a significant differentiating feature to the other Control Units of the SINAMICS G120 drive family.
The CU230P-2 Control Units can be operated with the following Power Modules:
PM240‑2
PM240
PM250
Note:
The CU230P‑2 is the Control Unit for SINAMICS G120P and SINAMICS G120P Cabinet for pumps, fans and compressors.
Please refer to Catalog D 35 for more information.
Note:
Shield plates and shield connection kits are available. These can be used in the wiring installation for the Control Units and Power Modules to ensure that it complies with EMC guidelines.
For more information about shield connection kits and shield plates for Control Units and Power Modules, please refer to section "Supplementary system components".
Typical, integrated HVAC/HLK functions
Linear and quadratic torque characteristic for fluid flow and positive displacement machines
ECO mode for additional energy saving in U/f control mode
2 analog inputs (current/voltage can be selected) to directly connect pressure/level sensors
2 additional analog inputs to connect Pt1000/LG‑Ni1000 temperature sensors
Direct control of valves and flaps using two 230 V AC relays
Automatic restart
Flying restart
Skip frequencies
Hibernation mode
Load check function to monitor belts and flow
Cascade connection
4 integrated PID controllers (e.g. for temperature, pressure, air quality, level)
Multi-zone controller
Essential service mode
Real time clock with three time generators
IOP wizards for special applications
Pumps: Positive displacement (constant load torque) and centrifugal pumps (square load torque) with and without PID controller
Fans: Radial and axial fans (square load torque) with and without PID controller
Compressors: Positive displacement (constant load torque) and fluid flow machines (square load torque) with and without PID controller
CU240E‑2 DP‑F Control Unit
The Control Unit performs closed-loop control functions for the inverter.
The CU240E‑2 Control Unit is designed as standard Control Unit for all of the usual applications involving U/f or vector control.
CU240E-2 series with standard I/O quantity structure and integrated safety technology
The CU240E‑2 Control Unit can be combined with the following Power Modules:
PM240‑2
PM240
PM250
Note:
Shield plates and shield connection kits are available. These can be used in the wiring installation for the Control Units and Power Modules to ensure that it complies with EMC guidelines.
For more information about shield connection kits and shield plates for Control Units and Power Modules, please refer to section "Supplementary system components".
Safety Integrated functions
The safety function "Safe Torque Off" (STO) (certified according to IEC 61508 SIL 2 and EN ISO 13849‑1 PL d and Category 3) is already integrated into the basic versions of the CU240E‑2 series (CU240E‑2, CU240E‑2 DP, CU240E‑2 PN).
With the fail-safe variants of the CU240E-2 series (CU240E‑2 F, CU240E‑2 DP-F, CU240E‑2 PN-F), the fail-safe SINAMICS G120 inverter provides five safety functions which are certified according to IEC 61508 SIL 2 and EN ISO 13849‑1 PL d and Category 3:
Safe Torque Off (STO)
to protect against active movement of the drive
Safe Stop 1 (SS1)
for continuous monitoring of a safe braking ramp
Safely Limited Speed (SLS)
for protection against dangerous movements when a speed limit is exceeded (the CU240E‑2 DP‑F Control Unit has up to 4 selectable SLS limit values)
Safe Direction (SDI)
This function ensures that the drive can only rotate in the selected direction.
Safe Speed Monitor (SSM)
This function signals if a drive operates below a specific speed/feed velocity (only CU240E‑2 DP‑F / CU240E‑2 PN‑F with PROFIsafe).
These functions can be activated by means of PROFIsafe or via the safety inputs.
None of the safety functions require a motor encoder and they are thus much cheaper and easier to implement. Existing systems in particular can be simply updated with safety technology without the need to change the motor or mechanical system.
The Safe Torque Off (STO) function can be used without restriction for all applications. The SS1, SLS, SDI and SSM functions are only permissible for applications where the load can never accelerate when the inverter is switched off. They are therefore not permitted for applications involving pull-through loads such as hoisting gear and unwinders.
Additional information is provided in chapter Highlights, section Safety Integrated.
CU250S-2 Control Unit
The Control Unit performs closed-loop control functions for the inverter.
The CU250S‑2 Control Units are designed as standard Control Units for all of the usual applications involving V/f or vector control.
CU250S‑2 Control Units can be used to implement all common applications involving V/f or vector control as well as applications for drives with positioning requirements. This expansion allows them to be used in lifting, swiveling, traversing or rotating applications. The positioning functionality is comparable with SINAMICS S110 servo drives.
Two points must be noted here:
Vector control (VC) and sensorless vector control (SLVC) are possible
Positioning possible via one encoder or in parallel using two encoders
The CU250S‑2 Control Units can be combined with the following Power Modules:
PM240‑2
PM240
PM250
Note:
Shield plates and shield connection kits are available for use in the wiring installation of Control Units and Power Modules to ensure that it complies with EMC guidelines.
For more information about shield connection kits and shield plates for Control Units and Power Modules, please refer to section "Supplementary system components".
Safety Integrated functions
The following Safety Integrated Basic Functions (certified according to IEC 61508 SIL 2 and EN ISO 13849‑1 PL d and Category 3) are integrated as standard in the CU250S-2 series:
Safe Torque Off (STO)
to protect against active movement of the drive
Safe Stop 1 (SS1)
for continuous monitoring of a safe braking ramp
Safe Brake Control (SBC) is used to safely control a holding
brake
The following Safety Integrated Extended Functions (certified according to IEC 61508 SIL 2 and EN ISO 13849‑1 PL d and Category 3) are optionally available for the CU250S-2 series:
Safely Limited Speed (SLS)
for protection against dangerous movements on exceeding a speed limit
Safe Direction (SDI)
This function ensures that the drive can only rotate in the selected direction.
Safe Speed Monitor (SSM)
This function signals if a drive operates below a specific speed/feed velocity.
These functions can be activated by means of PROFIsafe or via the safety inputs.
None of the safety functions require a motor encoder and they are thus much cheaper and easier to implement. Existing systems in particular can be simply updated with safety technology without the need to change the motor or mechanical system.
The Safe Torque Off (STO) function can be used without restriction for all applications. The SS1, SLS, SDI and SSM functions are only permissible for applications where the load can never accelerate when the inverter is switched off. They are therefore not permitted for applications involving pull-through loads such as hoisting gear and unwinders.
Additional information is provided in chapter Highlights, section Safety Integrated.
![]()
CU230P‑2 Control Unit with open and closed terminal covers
Terminal No. | Signal | Features |
|---|---|---|
Digital inputs (DI) – Standard | ||
69 | DI COM | Reference potential for digital inputs |
5 ... 8, | DI0 … DI5 | Freely programmable |
Digital outputs (DO) | ||
18 | DO0, NC | Relay output 1 |
19 | DO0, NO | Relay output 1 |
20 | DO0, COM | Relay output 1 |
21 | DO1, NO | Relay output 2 |
22 | DO1, COM | Relay output 2 |
23 | DO2, NC | Relay output 3 |
24 | DO2, NO | Relay output 3 |
25 | DO2, COM | Relay output 3 |
Analog inputs (AI) | ||
3 | AI0+ | Differential input, switchable between current, voltage |
4 | AI0- | |
10 | AI1+ | Differential input, switchable between current, voltage |
11 | AI1- | |
50 | AI2+ | Non-isolated input, switchable between current and temperature sensors, type Pt1000/LG-Ni1000 |
51 | GND | Reference potential of the AI2/internal electronics ground |
52 | AI3+ | Non-isolated input for temperature sensors, type Pt1000/LG‑Ni1000 |
53 | GND | Reference potential of the AI3/internal electronics ground |
Analog outputs (AO) | ||
12 | AO0+ | Non-isolated output |
13 | GND | Reference potential of the AO0/internal electronics ground |
26 | AO1+ | Non-isolated output |
27 | GND | Reference potential of the AO1/internal electronics ground |
PTC/KTY interface | ||
14 | T1 MOTOR | Positive input for motor temperature sensor |
15 | T2 MOTOR | Negative input for motor temperature sensor |
Power supply | ||
9 | +24 V OUT | Power supply output |
28 | GND | Reference potential of the power supply/internal electronics ground |
1 | +10 V OUT | Power supply output |
2 | GND | Reference potential of the power supply/internal electronics ground |
31 | +24 V IN | Power supply input |
32 | GND IN | Reference potential of the power supply input |
35 | +10 V OUT | Power supply output |
36 | GND | Reference potential of the power supply/internal electronics ground |
1) The following applies to systems complying with UL: A maximum of 3 A, 30 V DC or 2 A, 250 V AC may be connected via terminals 18 / 20 (DO0 NC) and 23 / 25 (DO2 NC).
CU240E‑2 Control Unit with open and closed terminal covers
Terminal No. | Signal | Features |
|---|---|---|
Digital inputs (DI) – Standard | ||
5 ... 8, | DI0 … DI5 | Freely programmable (isolated) 5.5 mA/24 V |
69 | DI COM1 | Reference potential for digital inputs |
34 | DI COM2 | Reference potential for digital inputs |
Digital inputs (DI) – Fail-safe | ||
16, 17 | F-DI0 | Fail-safe digital inputs, 2 channels (redundant), |
The following are only available for CU240E‑2 F, CU240E‑2 DP‑F and CU240E‑2 PN‑F | ||
5, 6 | F-DI0 | Fail-safe digital inputs, 2 channels (redundant), |
7, 8 | F-DI1 | Fail-safe digital inputs, 2 channels (redundant), |
16, 17 | F-DI2 | Fail-safe digital inputs, 2 channels (redundant), |
Digital outputs (DO) | ||
18 | DO0, NC | Relay output DO0 |
19 | DO0, NO | Relay output DO0 |
20 | DO0, COM | Relay output DO0 |
21 | DO1+ | Transistor output DO1 |
22 | DO1- | Transistor output DO1 |
23 | DO2, NC | Relay output DO2 |
24 | DO2, NO | Relay output DO2 |
25 | DO2, COM | Relay output DO2 |
Analog inputs (AI) | ||
3 | AI0+ | Differential input, switchable between current, voltage |
4 | AI0- | |
10 | AI1+ | Differential input, switchable between current, voltage |
11 | AI1- | |
Analog outputs (AO) | ||
12 | AO0+ | |
内蒙古省供货地区:
呼和浩特市 包头市 乌海市 赤峰市 通辽市 鄂尔多斯市 呼伦贝尔市 巴彦淖尔市 锡林郭勒盟
新疆自治区供货地区:
乌鲁木齐市 石河子市 克拉玛依市 和田市 阿图仕市 阿克苏市 喀什市 库尔勒市 吐鲁番市
西藏自治区供货地区:
拉萨 林芝 昌都 日喀则
云南省供货地区:
昆明市 曲靖市 玉溪市 丽江市 普洱市 保山市 昭通市 临沧市
贵州省供货地区:
贵阳市 遵义市 安顺市 凯里市 铜仁市 毕节市 都匀市 六盘水市 兴义市
四川省供货地区:
成都市 自贡市 攀枝花市 泸州市 德阳市 绵阳市 广元市 遂宁市 内江市 乐山市 南充市 宜宾市 广安市 达州市 巴中市 雅安市 眉山市 资阳市
广西省供货地区:
南宁市 桂林市 柳州市 梧州市 钦州市 北海市 玉林市 贵港市 防城港市 百色市 来宾市
电源模板
6ES72881SR200AA0
6ES72881ST200AA0
6ES72881SR300AA0
6ES72881ST300AA0
6ES72881SR400AA0
6ES72881ST400AA0
6ES72881SR600AA0
6ES72881ST600AA0
6ES72881CR400AA0
6ES72881CR600AA0
6ES72882DE080AA0
6ES72882DR080AA0
6ES72882DT080AA0
6ES72882DR160AA0
6ES72882DT160AA0
6ES72882DR320AA0
6ES72882DT320AA0
6ES72883AE040AA0
6ES72883AE080AA0
6ES72883AQ020AA0
6ES72883AQ040AA0
6ES72883AM030AA0
6ES72883AM060AA0
6ES72883AR020AA0
6ES72883AR040AA0
6ES72883AT040AA0
6ES72887DP010AA0
6ES72880CD100AA0
6ES72880ED100AA0
6ES72885CM010AA0
6ES72885DT040AA0
6ES72885AE010AA0
6ES72885AQ010AA0
6ES72885BA010AA0
6AV66480BC113AX0
6AV66480BE113AX0
6AV66480CC113AX0
6AV66480CE113AX0
6ES72110AA230XB0
6ES72110BA230XB0
6ES72121AB230XB0
6ES72121BB230XB0
6ES72141AD230XB0
6ES72141BD230XB0
6ES72142AD230XB0
6ES72142AS230XB0
6ES72142BD230XB0
6ES72162AD230XB0
6ES72162BD230XB0
6ES72121AB230XB8
6ES72121BB230XB8
6ES72141AD230XB8
6ES72141BD230XB8
6ES72142AD230XB8
6ES72142AS230XB8
6ES72142BD230XB8
6ES72162AD230XB8
6ES72162BD230XB8
6ES72211BF220XA0
6ES72211BH220XA0