西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商
)Factory setting: not activated (can be parameterized)
2) This function requires an additional external circuit.
上海昊征自动化科技有限公司
联系人:颜江
手机:
电话:
传真:
Q Q:455499155
企业邮箱:xmz169@qq.com
Power unit protection |
De |
---|---|
Ground fault monitoring at output end |
A ground fault at the output end is detected by a summation current monitor and results in shutdown in grounded systems. |
Electronic short-circuit protection at the output end |
A short-circuit at the output end (e.g. at the converter output terminals, in the motor cable or in the motor terminal box) is detected and the converter shuts down with "fault". |
Thermal overload protection |
An alarm is issued first when the overtemperature threshold responds. If the temperature rises further, the unit independently adjusts the pulse frequency or output current so that a reduction in the thermal load is achieved. Once the cause of the fault has been eliminated (e.g. cooling has been improved), the original operating values are automatically resumed. |
The table below lists the recommended and maximum possible cable connections at the line and motor ends (versions A and C).
The recommended cross-sections are
When the conditions differ from those specified above (cable routing, cable grouping, ambient temperature), the appropriate correction factors according to IEC 60364‑5‑52 must be taken into account.
Rated power |
Converter |
Line supply connection |
Motor connection |
Cabinet grounding |
|||||
---|---|---|---|---|---|---|---|---|---|
400 V/690 V |
SINAMICS G120P Cabinet versions A and C |
Recommended cross-section 1) |
Maximum conductor cross-section |
Fixing screw |
Recommended cross-section 1) |
Maximum conductor cross-section |
Fixing screw |
Maximum conductor cross-section |
Fixing screw |
|
|
IEC |
IEC |
|
IEC |
IEC |
|
IEC |
|
kW |
6SL3710‑ ... |
mm2 |
mm2 |
|
mm2 |
mm2 |
|
mm2 |
|
380 ... 480 V 3 AC |
|||||||||
75 |
1PE31-5AB0-Z |
50 |
2 × 120 |
M12 |
50 |
2 × 120 |
M12 |
2 × 120 |
M12 |
90 |
1PE31-8AB0-Z |
70 |
70 |
||||||
110 |
1PE32-1AB0-Z |
95 |
95 |
||||||
132 |
1PE32-5AB0-Z |
95 |
2 × 50 |
||||||
160 |
1PE33-0 . A0-Z |
2 × 120 |
2 × 240 |
2 × 95 |
2 × 240 |
M12 x 40 2) |
3 × 240 |
||
200 |
1PE33-7 . A0-Z |
2 × 120 |
2 × 95 |
||||||
250 |
1PE34-6 . A0-Z |
2 x 185 |
2 x 150 |
||||||
315 |
1PE35-8 . A0-Z |
2 x 240 |
4 × 240 |
2 x 185 |
4 x 240 |
6 x 240 |
|||
355 |
1PE36-6 . A0-Z |
3 x 150 |
2 x 240 |
||||||
400 |
1PE37-4 . A0-Z |
3 x 185 |
2 x 240 |
||||||
450 |
1PE38-4AA0-Z |
4 x 185 |
6 × 240 |
4 × 150 |
4 x 240 |
6 × 240 |
|||
500 |
1PE38-8AA0-Z |
4 x 185 |
4 × 150 |
6 × 240 |
|||||
560 |
1PE41-0AA0-Z |
4 x 240 |
4 × 150 |
||||||
500 ... 690 V 3 AC |
|||||||||
315 |
1PG33-7 . A0-Z |
2 x 120 |
4 × 240 |
M12 |
2 × 120 |
4 x 240 |
M12 x 40 2) |
6 × 240 |
M12 |
355 |
1PG34-0 . A0-Z |
2 x 150 |
2 × 120 |
||||||
400 |
1PG34-5 . A0-Z |
2 x 185 |
2 x 150 |
||||||
450 |
1PG35-2 . A0-Z |
3 x 120 |
3 x 95 |
||||||
500 |
1PG35-8AA0 |
2 x 240 |
6 × 240 |
2 x 185 |
4 x 240 |
||||
560 |
1PG36-5AA0 |
3 x 185 |
2 x 240 |
||||||
630 |
1PG37-2AA0 |
3 x 185 |
2 x 240 |
1) The recommendations for the North American market in AWG or MCM should be taken from the appropriate NEC (National Electrical Code) or CEC (Canadian Electrical Code) standards.
2) The connecting blocks can be damaged when using longer screws.
It is always recommended to use shielded - for higher power ratings - where possible symmetrical, 3-wire three-phase cables between the converter and the motor, and where required, to connect several of these cables in parallel. There are essentially 2 reasons for this:
The cable cross-section required depends on the current being conducted in the cable. The permissible current loading of cables is defined, for example, in IEC 60364‑5‑52. It depends on ambient conditions, such as temperature, but also on the routing method. It should be taken into account as to whether cables are routed individually and therefore relatively well ventilated, or whether groups of cables are routed together. In the latter case, the cables have significantly poorer ventilation and can therefore heat one another up more significantly. For the relevant correction factors applicable to these boundary conditions, please refer to IEC 60364‑5‑52.
The table below provides a guide to the recommended cross-sections (
Current-carrying capacity according to IEC 60364‑5‑52 at 40 °C (104 °F)
Cross-section 3-wire cable |
Copper cable |
Aluminum cable |
||
---|---|---|---|---|
|
Single routing |
Several cables lying next to one another 1) |
Single routing |
Several cables lying next to one another 1) |
mm2 |
A |
A |
A |
A |
3 × 2.5 |
22 |
17 |
17 |
13 |
3 × 4 |
30 |
23 |
23 |
18 |
3 × 6 |
37 |
29 |
29 |
22 |
3 × 10 |
52 |
41 |
40 |
31 |
3 × 16 |
70 |
54 |
53 |
41 |
3 × 25 |
88 |
69 |
68 |
53 |
3 × 35 |
110 |
86 |
84 |
65 |
3 × 50 |
133 |
104 |
102 |
79 |
3 × 70 |
171 |
133 |
131 |
102 |
3 × 95 |
207 |
162 |
159 |
124 |
3 × 120 |
240 |
187 |
184 |
144 |
3 × 150 |
278 |
216 |
213 |
166 |
3 × 185 |
317 |
247 |
244 |
190 |
3 × 240 |
374 |
292 |
287 |
224 |
1)A maximum of 9 cables may be routed directly next to one another horizontally on a cable tray.
Cables must be connected in parallel for higher currents.
Note:
The recommendations for the North American market in AWG or MCM should be taken from the corresponding standards NEC (National Electrical Code) or CEC (Canadian Electrical Code).
The protective conductor must be dimensioned taking into account the following data:
Cross-section, line conductor |
Minimum cross-section, external protective conductor |
---|---|
mm2 |
mm2 |
up to 16 |
Minimum cross-section of external conductor |
16 ... 35 |
16 |
from 35 |
At least half the cross-section of external conductor |
Note:
The recommendations for the North American market in AWG or MCM should be taken from the corresponding standards NEC (National Electrical Code) or CEC (Canadian Electrical Code).
Switchgear and motors are usually grounded separately via a local ground electrode. With this constellation, the ground fault current flows via the parallel ground connections and is divided. In spite of the relatively small protective conductor cross-sections used in accordance with the table above, no inadmissible touch voltages occur with this grounding system.
However, from experience gained with different grounding constellations, we recommend that the ground cable from the motor returns directly to the converter. For EMC reasons and to prevent bearing currents – for higher power ratings – symmetrical, 3-wire, three-phase cables should be preferentially used instead of four-wire cables. For 3-wire cables, the protection or PE wire must be routed separately or arranged symmetrically in the motor cable. The symmetry of the PE conductor is achieved using a conductor surrounding all phase conductors or using a cable with a symmetrical arrangement of the three phase conductors and three ground conductors.
Through their high-speed controllers, the converters limit the load current (motor and ground fault currents) to an rms value corresponding to the rated current. We therefore recommend the use of a PE conductor cross-section analogous to the phase conductor cross-section for grounding the control cabinet.
The most important directives and standards are listed below. These are used as basis for the SINAMICS G120P Cabinet converter cabinet units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.
European directives |
|
2014/35/EU |
Low-voltage directive: Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states relating to the provision of electrical equipment designed for use within certain voltage limits on the market (amended version) |
2014/30/EU |
EMC directive: Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states relating to electromagnetic compatibility (amended version) |
2006/42/EC |
Machinery directive: The directive of the European Parliament and Council of May 17, 2006 on machinery and for changing Directive 95/16/EC (amendment) |
European standards |
|
EN 60146‑1‑1 |
Semiconductor converters – General requirements and line-commutated converters Part 1‑1: Specification of basic requirements |
EN 60204‑1 |
Electrical equipment of machines Part 1: General requirements |
EN 60529 |
Degrees of protection provided by enclosures (IP code) |
EN 61800‑2 |
Adjustable speed electrical power drive systems Part 2: General requirements – Rating specifications for low-voltage adjustable frequency a.c. power drive systems |
EN 61800‑3 |
Adjustable speed electrical power drive systems Part 3: EMC product standard including specific test methods |
EN 61800-5-1 |
Adjustable speed electrical power drive systems Part 5: Safety requirements Main section 1: Electrical and thermal requirements |
西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商西门子数控备件6FC5247-0AA11-0AA0代理商