如接线安定,可拆下接线端丈量有无24VDC。假如在电磁阀接线端丈量有24V,此刻需验证电磁阀线圈是否烧坏,假如开路。此外,绷簧过硬,反作用力过大,线圈匝数太少,吸力不行也可使得线圈焚毁。紧急处理时,可将线圈上的手动按钮由正常作业时的“0" 位打到“1"位,使得阀翻开。假定M671线圈损坏,此刻需手动切换M671的出气路,翻开V671,使再生气行成通路由V671→V676→放空,在技术允许时再更换M671的线圈。
hydac贺德克电磁阀卡住。假如M671带电,而电磁阀无法切换作业。先确认电磁阀的气源压力是否到达规范值。假如压力满足,则可能是电磁阀气路阻塞或卡住。首先把备用气路元件换上,正常投用使电磁阀作业,主动翻开V671。然后将阻塞的气路元件取出阀芯及阀芯套用CCI4清洁,再抹上润滑脂。