Article number
|
6ES7410-5HX08-0AB0
|
6ES7410-5HM08-0AB0
|
|
PCS 7 CPU410-5H F. S7-400/S7-400H/F/FH
|
PCS 7 CPU 410E F. S7-400/S7-400H/F/FH
|
General information
|
|
|
Product type designation
|
CPU 410-5H
|
CPU 410E
|
HW functional status
|
2
|
1
|
Firmware version
|
V8.2
|
V8.2
|
Design of PLC basic unit
|
With Conformal Coating (ISA-S71.04 severity level G1; G2; G3) and operating temperature to 70 °C
|
With Conformal Coating (ISA-S71.04 severity level G1; G2; G3) and operating temperature to 70 °C
|
Product function
|
|
|
SysLog
|
Yes; via TCP; up to 4 receivers can be parameterized; buffer capacity max. 3 200 entries
|
Yes; via TCP; up to 4 receivers can be parameterized; buffer capacity max. 3 200 entries
|
Field interface security
|
Yes
|
Yes
|
Engineering with
|
|
|
Programming package
|
SIMATIC PCS 7 V9.0 or higher
|
SIMATIC PCS 7 V9.0 or higher
|
CiR – Configuration in RUN
|
|
|
CiR synchronization time, basic load
|
60 ms
|
60 ms
|
CiR synchronization time, time per I/O byte
|
0 µs
|
0 µs
|
Input current
|
|
|
from backplane bus 5 V DC, typ.
|
2 A
|
2 A
|
from backplane bus 5 V DC, max.
|
2.4 A
|
2.4 A
|
from backplane bus 24 V DC, max.
|
150 mA; DP interface
|
150 mA; DP interface
|
from interface 5 V DC, max.
|
90 mA; At the DP interface
|
90 mA; At the DP interface
|
Power loss
|
|
|
Power loss, typ.
|
10 W
|
10 W
|
Processor
|
|
|
CPU speed
|
450 MHz; Multi-processor system
|
450 MHz; Multi-processor system
|
Memory
|
|
|
PCS 7 process s
|
100 ... approx. 2 600, adjustable with System Expansion Card
|
200; max.
|
Work memory
|
|
|
integrated
|
32 Mbyte; max., dependent on the System Expansion Card used
|
4 Mbyte
|
integrated (for program)
|
Dependent on the System Expansion Card used
|
4 Mbyte; max.
|
integrated (for data)
|
Dependent on the System Expansion Card used
|
4 Mbyte; max.
|
expandable
|
Dependent on the System Expansion Card used
|
No
|
Load memory
|
|
|
integrated RAM, max.
|
48 Mbyte
|
48 Mbyte
|
expandable RAM
|
No
|
No
|
Backup
|
|
|
present
|
Yes
|
Yes
|
with battery
|
Yes; all data
|
Yes; all data
|
without battery
|
Yes; Program and data of the load memory
|
Yes; Program and data of the load memory
|
Battery
|
|
|
Backup battery
|
|
|
Backup current, typ.
|
370 µA; Valid up to 40°C
|
370 µA; Valid up to 40°C
|
Backup current, max.
|
2.1 mA
|
2.1 mA
|
Backup time, max.
|
Dealt with in the module data manual with the secondary conditions and the factors of influence
|
Dealt with in the module data manual with the secondary conditions and the factors of influence
|
Feeding of external backup voltage to CPU
|
No
|
No
|
CPU processing times
|
|
|
for bit operations, typ.
|
7.5 ns
|
7.5 ns
|
for word operations, typ.
|
7.5 ns
|
7.5 ns
|
for fixed point arithmetic, typ.
|
7.5 ns
|
7.5 ns
|
for floating point arithmetic, typ.
|
15 ns
|
15 ns
|
average processing time of PCS 7 typicals
|
110 µs; with APL Typicals
|
110 µs; with APL Typicals
|
Process tasks, max.
|
9; Individually adjustable from 10 ms to 5 s
|
9; Individually adjustable from 10 ms to 5 s
|
CPU-blocks
|
|
|
DB
|
|
|
Number, max.
|
16 000; Number range: 1 to 16 000 (= Instances)
|
16 000; Number range: 1 to 16 000 (= Instances)
|
Size, max.
|
Dependent on the System Expansion Card used
|
Dependent on the System Expansion Card used
|
FB
|
|
|
Number, max.
|
8 000; Number range: 0 to 7999
|
8 000; Number range: 0 to 7999
|
Size, max.
|
64 kbyte
|
64 kbyte
|
FC
|
|
|
Number, max.
|
8 000; Number range: 0 to 7999
|
8 000; Number range: 0 to 7999
|
Size, max.
|
64 kbyte
|
64 kbyte
|
OB
|
|
|
Number, max.
|
see instruction list
|
see instruction list
|
Size, max.
|
64 kbyte
|
64 kbyte
|
Number of free cycle OBs
|
1; OB 1
|
1; OB 1
|
Number of time alarm OBs
|
8; OB 10-17
|
8; OB 10-17
|
Number of delay alarm OBs
|
4; OB 20-23
|
4; OB 20-23
|
Number of cyclic interrupt OBs
|
9; OB 30-38 (= Process Tasks)
|
9; OB 30-38 (= Process Tasks)
|
Number of process alarm OBs
|
8; OB 40-47
|
8; OB 40-47
|
Number of DPV1 alarm OBs
|
3; OB 55-57
|
3; OB 55-57
|
Number of startup OBs
|
2; OB 100, 102
|
2; OB 100, 102
|
Number of asynchronous error OBs
|
9; OB 80-88
|
9; OB 80-88
|
Number of synchronous error OBs
|
2; OB 121, 122
|
2; OB 121, 122
|
Nesting depth
|
|
|
per priority class
|
24
|
24
|
additional within an error OB
|
2
|
2
|
Counters, timers and their retentivity
|
|
|
S7 counter
|
|
|
Number
|
2 048
|
2 048
|
Retentivity
|
|
|
— adjustable
|
Yes
|
Yes
|
Counting range
|
|
|
— lower limit
|
0
|
0
|
— upper limit
|
999
|
999
|
IEC counter
|
|
|
Number
|
Unlimited (limited only by RAM capacity)
|
Unlimited (limited only by RAM capacity)
|
S7 times
|
|
|
Number
|
2 048
|
2 048
|
Retentivity
|
|
|
— adjustable
|
Yes
|
Yes
|
Time range
|
|
|
— lower limit
|
10 ms
|
10 ms
|
— upper limit
|
9 990 s
|
9 990 s
|
IEC timer
|
|
|
present
|
Yes
|
Yes
|
Type
|
SFB
|
SFB
|
Number
|
Unlimited (limited only by RAM capacity)
|
Unlimited (limited only by RAM capacity)
|
Data areas and their retentivity
|
|
|
retentive data area in total
|
Total working and load memory (with backup battery)
|
Total working and load memory (with backup battery)
|
Flag
|
|
|
Number, max.
|
16 384 byte
|
16 384 byte
|
Retentivity available
|
Yes
|
Yes
|
Number of clock memories
|
8; in 1 memory byte
|
8; in 1 memory byte
|
Local data
|
|
|
adjustable, max.
|
64 kbyte
|
64 kbyte
|
preset
|
64 kbyte
|
64 kbyte
|
Address area
|
|
|
I/O address area
|
|
|
Inputs
|
16 kbyte; max., dependent on the System Expansion Card used
|
2 048 byte; Max. 1 536 bytes can be used for input or output data
|
Outputs
|
16 kbyte; max., dependent on the System Expansion Card used
|
2 048 byte; Max. 1 536 bytes can be used for input or output data
|
of which distributed
|
|
|
— DP interface, inputs
|
6 kbyte; max., dependent on the System Expansion Card used
|
1 536 byte; max.
|
— DP interface, outputs
|
6 kbyte; max., dependent on the System Expansion Card used
|
1 536 byte; max.
|
— PROFINET interface, inputs
|
8 kbyte; max., dependent on the System Expansion Card used
|
1 536 byte; max.
|
— PROFINET interface, outputs
|
8 kbyte; max., dependent on the System Expansion Card used
|
1 536 byte; max.
|
Process image
|
|
|
Inputs, adjustable
|
16 kbyte
|
2 048 byte
|
Outputs, adjustable
|
16 kbyte
|
2 048 byte
|
Inputs, default
|
16 kbyte; Total peripheral address range, cannot be changed
|
2 048 byte; Total peripheral address range, cannot be changed
|
Outputs, default
|
16 kbyte; Total peripheral address range, cannot be changed
|
2 048 byte; Total peripheral address range, cannot be changed
|
consistent data, max.
|
244 byte
|
244 byte
|
Access to consistent data in process image
|
Yes
|
Yes
|
Subprocess images
|
|
|
Number of subprocess images, max.
|
15
|
15
|
Digital channels
|
|
|
Inputs
|
131 072; max., dependent on the System Expansion Card used
|
16 384; max.
|
— of which central
|
131 072; max., dependent on the System Expansion Card used
|
16 384; max.
|
Outputs
|
131 072; max., dependent on the System Expansion Card used
|
16 384; max.
|
— of which central
|
131 072; max., dependent on the System Expansion Card used
|
16 384; max.
|
Analog channels
|
|
|
Inputs
|
8 192; max., dependent on the System Expansion Card used
|
1 024; max.
|
— of which central
|
8 192; max., dependent on the System Expansion Card used
|
1 024; max.
|
Outputs
|
8 192; max., dependent on the System Expansion Card used
|
1 024; max.
|
— of which central
|
8 192; max., dependent on the System Expansion Card used
|
1 024; max.
|
Hardware configuration
|
|
|
Number of expansion units, max.
|
21; S7-400 expansion devices
|
|
connectable OPs
|
119
|
119
|
Multicomputing
|
No
|
No
|
Interface modules
|
|
|
Number of connectable IMs (total), max.
|
6
|
|
Number of connectable IM 460s, max.
|
6
|
|
Number of connectable IM 463s, max.
|
4; Single mode only
|
|
Number of DP masters
|
|
|
integrated
|
1
|
1
|
via CP
|
10; CP 443-5 Extended
|
4; CP 443-5 Extended
|
Number of IO Controllers
|
|
|
integrated
|
2
|
2
|
via CP
|
0
|
0
|
Number of operable FMs and CPs (recommended)
|
|
|
CP, LAN
|
|
4
|
PROFIBUS and Ethernet CPs
|
11; Of which max. 10 CP as DP master
|
4
|
Slots
|
|
|
required slots
|
2
|
2
|
Time of day
|
|
|
Clock
|
|
|
Hardware clock (real-time)
|
Yes
|
Yes
|
retentive and synchronizable
|
Yes
|
Yes
|
Resolution
|
1 ms
|
1 ms
|
Deviation per day (buffered), max.
|
1.7 s; Power off
|
1.7 s; Power off
|
Deviation per day (unbuffered), max.
|
8.6 s; Power on
|
8.6 s; Power on
|
Operating hours counter
|
|
|
Number
|
16
|
16
|
Number/Number range
|
0 to 15
|
0 to 15
|
Range of values
|
SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours
|
SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours
|
Granularity
|
1 h
|
|
retentive
|
Yes
|
Yes
|
Clock synchronization
|
|
|
supported
|
Yes
|
Yes
|
to DP, master
|
Yes
|
Yes
|
to DP, slave
|
Yes
|
Yes
|
in AS, master
|
Yes
|
Yes
|
in AS, slave
|
Yes
|
Yes
|
on Ethernet via NTP
|
Possible as client and master/slave via SIMATIC process
|
Possible as client and master/slave via SIMATIC process
|
Interfaces
|
|
|
Number of PROFINET interfaces
|
2
|
2
|
Number of RS 485 interfaces
|
1; PROFIBUS DP
|
1; PROFIBUS DP
|
Number of other interfaces
|
2; 2x synchronization
|
2; 2x synchronization
|
1. Interface
|
|
|
Interface type
|
Integrated
|
Integrated
|
Physics
|
RS 485 / PROFIBUS
|
RS 485 / PROFIBUS
|
Isolated
|
Yes
|
Yes
|
Power supply to interface (15 to 30 V DC), max.
|
150 mA
|
150 mA
|
Number of connection resources
|
16
|
16
|
Functionality
|
|
|
PROFIBUS DP master
|
Yes
|
Yes
|
PROFIBUS DP slave
|
No
|
No
|
DP master
|
|
|
Number of connections, max.
|
16
|
16
|
Transmission rate, max.
|
12 Mbit/s
|
12 Mbit/s
|
Number of DP slaves, max.
|
96
|
96
|
Number of slots per interface, max.
|
1 632
|
1 632
|
Services
|
|
|
— PG/OP communication
|
Yes
|
Yes
|
— Routing
|
Yes; S7 routing
|
Yes; S7 routing
|
— Global data communication
|
No
|
No
|
— S7 basic communication
|
No
|
No
|
— S7 communication
|
Yes
|
Yes
|
— S7 communication, as client
|
Yes
|
Yes
|
— S7 communication, as server
|
Yes
|
Yes
|
— Equidistance
|
No
|
No
|
— Isochronous mode
|
No
|
No
|
— SYNC/FREEZE
|
No
|
No
|
— Activation/deactivation of DP slaves
|
Yes; Approved for stand-alone operation only, not in conjunction with CiR (Configuration in Run)
|
Yes; Single mode only
|
— Direct data exchange (slave-to-slave
|